Mitsubishi Ecodan Fault P2: Liquid Refrigerant Thermistor (TH2)
Affected Models: Mitsubishi Ecodan Split Hydroboxes & Cylinders (EHSC, EHST, ERSC, ERST with PUHZ-SW / SHW)
⚡ Quick Engineering Answer
Mitsubishi Electric Ecodan • Fault Code P2Mitsubishi Ecodan Fault Code P2 means the controller detected an open or short circuit on liquid refrigerant pipe thermistor TH2 inside the indoor hydrobox or cylinder. Because TH2 tracks phase change across the plate exchanger, heating halts until a technician inspects the plug, clears corrosion, or replaces the external TH2 probe.
📊 Technical Specification & Trigger Matrix
- Official Manual Definition
- Indoor liquid refrigerant pipe thermistor TH2 measured an electrical open or short circuit.
- Trigger Threshold
- TH2 reads <-40°C (open) or >90–150°C (short) for >5 sec
- Recovery Window
- Manual reset after repairing TH2 sensor or harness
- Subsystem Affected
- Liquid Refrigerant Pipe Thermistor (TH2)
- Warranty Outlook
- OEM TH2 thermistor covered inside warranty window
How Mitsubishi Electric Ecodan Fault Code P2 Triggers
While water thermistors log under L5, Ecodan's P-series faults pinpoint refrigerant-side sensors attached to the indoor plate heat exchanger. Thermistor TH2 sits inside a small copper well strapped to the liquid refrigerant pipe exiting or feeding the indoor exchanger.
Accurate TH2 telemetry coordinates expansion valve control and safeguards exchanger plates during cold outdoor defrost reversals. Condensation creeping inside torn Armaflex pipe insulation frequently corrodes TH2's resin capsule, or vibration snaps fine leads at the PCB plug, locking the unit in P2.
🔀 Hardware & Series Differences
Condensation during defrost wets unsealed copper wells rapidly.
Check exact 10kΩ vs 50kΩ NTC thermistor chart per revision.
🔍 Observable Symptoms
- •Controller stops with Fault P2 at power-up or mid-defrost.
- •Compressor refuses space heating and DHW cylinder operation.
- •Service Menu TH2 value displays dashes (---) or -40°C.
- •Damp lagging around indoor refrigerant connections.
⚙️ Ranked Root Causes
Torn pipe insulation traps defrost condensation inside downward pockets.
Poor pin contact after servicing interrupts low-voltage sensing.
Line vibration slowly rubs thin sensor insulation bare.
Shorted wiring damages PCB pull-up electronics.
🔄 Safe Shutdown & Reset Sequence Flow
Follow strict step order left-to-rightCheck front controller diagnostics to confirm anomalous -40°C reading.
Turn OFF indoor and outdoor switches 60s, then power outdoor ON first and indoor second.
Stop toggling breakers if P2 returns immediately and call an engineer.
High-Voltage / Refrigerant Safety Boundary: Pro Service Split
Steps tagged "Homeowner Safe" below are strictly external read-only or external breaker inspections. Steps tagged "Licensed Technician" involve energized DC/AC bus voltages, isolation testing, or sealed refrigerant circuits—never attempt those steps without certification.
🔧 Interactive Step-by-Step Diagnostic Checklist
Read Live TH2 Data on Front Panel
Check Running Information on the front screen without opening panels to verify TH2 shows impossible values while THW water sensors look normal.
Execute One Cold Power Cycle
Isolate indoor and outdoor breakers for 60 seconds, then restore outdoor ON first and indoor ON second.
Measure TH2 Resistance Cold & Hot
Isolate power safely, remove cover, unplug TH2 connector from indoor board, and measure kΩ resistance against copper pipe temperature.
Fit New OEM TH2 & Seal Vapor Barrier
Clean copper pocket, fit OEM TH2 sensor with retaining clip and thermal grease, and reseal closed-cell pipe lagging tightly.
📋 Ready-to-Send Technician Fault Brief
Completed safe checks without clearing Fault Code P2? Copy this structured engineering summary for your installer or OEM RMA ticket.
🧰 Field Reference: What Your Technician Will Inspect
For homeowner safety, DIY replacement tools are disabled on this fault code. Your F-Gas / HVAC technician should bring:
- •Digital Multimeter (kΩ range)
- •OEM Mitsubishi TH2 Thermistor
- •Closed-Cell Insulation Tape
Do Not Attempt Sealed Loop Repairs on Mitsubishi Electric Ecodan Fault Code P2
This fault involves pressurized refrigerant lines, compressor inverter boards, or internal hydronic controls. Under F-Gas, EPA Section 608, and OEM warranty rules, opening sealed refrigeration or pump chassis requires certified pros. Get competitive quotes from HVAC & heat pump specialists in your postal area:
❓ Frequently Asked Questions
Does fixing Fault P2 require draining F-Gas refrigerant?
No. TH2 sits externally in a dry sealed copper pocket on the pipe wall, so technicians replace it without opening sealed refrigerant lines.
Is P2 caused by dirty central heating water filters?
No. P2 strictly flags an electrical open or short circuit on the TH2 refrigerant pipe sensor.
Can condensation cause Fault P2?
Yes. Defrost condensation trickling down poorly insulated cold lines enters unsealed pockets and corrodes TH2 leads.
Related Mitsubishi Electric Ecodan Fault Codes
Refrigerant pipe temperature failed expected change across the plate heat exchanger during active heating or defrost.
FTC control board measured an out-of-range voltage, unplugged harness, or short on a THW water thermistor.
Primary heating water temperature inside the plate heat exchanger dropped toward freezing due to stalled or restricted circulation.
FTC detected negligible water temperature gain between THW1 flow and THW2 return despite sustained heating demand.