Deye Error F22: Emergency Stop / Remote Shutdown (Hybrid)
Affected Models: Deye SUN-SG04LP1, SUN-SG04LP3, SG05LP1, SG01HP3 & SUN-G03 String Inverters
⚡ Quick Engineering Answer
Deye • Error F22On Deye hybrid inverters (SG04LP1/LP3), Error F22 (Tz_EmergS_Fault) means an Emergency Stop, Rapid Shutdown (RSD) transmitter, or external remote shutdown contact is holding the inverter offline—it is NOT overheating (Igbt heat is F64). Note on three-phase SUN-G03 string units, F22 instead signals transient leakage or Phase Sequence error. Check external red E-Stop buttons safely first.
📊 Technical Specification & Trigger Matrix
- Official Manual Definition
- Inverter received an active Emergency Stop / Rapid Shutdown signal on hybrids, or phase/leakage alert on string units.
- Trigger Threshold
- External RSD/Emergency Stop dry contact asserted or remote Modbus stop bit held active
- Recovery Window
- Clears once external button releases or remote command clears; resets with power cycle
- Subsystem Affected
- RSD / Emergency Stop Terminal & Remote I/O
- Warranty Outlook
- External button bumped/tripped or installer RSD loop issue (rarely hardware)
How Deye Error F22 Triggers
Deye hybrid manuals designate Error F22 explicitly as Tz_EmergS_Fault (Emergency Stop / Remote Shutdown). Inside Deye's multi-function external communication/I-O terminal strip sits an Emergency Stop / Rapid Shutdown input loop alongside Dry Contact / Remote ON-OFF pins. When firefighters press an exterior rooftop RSD mushroom button, when a lithium battery rack smoke detector opens an interlock, or when an EMS/Smart Home relays a remote stop command, the inverter trips Error F22 immediately to kill hazardous AC and DC energy.
Watch out for model differences: on select three-phase string inverters (such as SUN-G03 models lacking hybrid RSD terminals), firmware maps F22 to Transient Leakage or Phase Sequence Fault. Always verify your unit series and check external red Rapid Shutdown / Emergency buttons before digging deeper.
🔀 Hardware & Series Differences
Inspect exterior red RSD button (twisted/pulled out) and remote shutdown terminal wiring.
Verify L1/L2/L3 clockwise rotation if newly installed string unit reports F22.
🔍 Observable Symptoms
- •Touchscreen displays Error F22 cleanly with zero thermal fan noise or scorched parts.
- •Unit stays completely idle with 0W solar export and disabled backup loads.
- •Red outdoor Rapid Shutdown mushroom button found pushed inward.
- •Triggers spontaneously if homeowner accidentally tapped Remote Shutdown inside an app/EMS.
⚙️ Ranked Root Causes
Kids, yard equipment, or wall knocks depress latched outdoor E-stop switches requiring twist-to-release.
Vibration opens normally-closed safety dry contacts or unplugs 24V RSD transmitter feed.
Automated demand-response scripts or wrong inverter setting checks trigger remote stop.
Incorrect grid phase order on legacy G03 grid-tie firmware surfaces under F22.
🔄 Safe Shutdown & Reset Sequence Flow
Follow strict step order left-to-rightCheck if a red push-button outside near your electricity meter was pressed in; twist clockwise to pop back out.
Verify no automated demand-response app or remote installer disabled inverter output.
After popping out an RSD switch, run a clean external power cycle if F22 stays displayed.
High-Voltage / Refrigerant Safety Boundary: Pro Service Split
Steps tagged "Homeowner Safe" below are strictly external read-only or external breaker inspections. Steps tagged "Licensed Technician" involve energized DC/AC bus voltages, isolation testing, or sealed refrigerant circuits—never attempt those steps without certification.
🔧 Interactive Step-by-Step Diagnostic Checklist
Check Exterior Rapid Shutdown / Emergency Stop Mushroom Button
Walk outdoors beside your utility meter or inverter wall and inspect any red 'PV Rapid Shutdown' or 'Emergency Stop' push-button—if depressed, twist gently following its arrows so the red cap springs outward.
Check Solarman / BMS App & Remote ON-OFF Menus
Verify in Deye Cloud/Solarman or smart-home automations (Home Assistant, Solar Assistant) that no 'Power Off' or remote shutdown command was sent inadvertently.
Inspect RSD Transmitter, Remote I/O Pins & LCD Pinout Bridge
Isolate unit safety power, open lower wiring compartment, check 24V RSD transmitter supply/fuses and pin seating on Emergency Stop / BMS interlock dry contacts; test continuity across E-stop switch.
Verify Advanced Function Enable Bits & Firmware
Check Deye touchscreen Advanced Settings for inadvertent 'Remote Lock / External Stop' toggles; clear locked status bit and test full startup.
📋 Ready-to-Send Technician Fault Brief
Completed safe checks without clearing Error F22? Copy this structured engineering summary for your installer or OEM RMA ticket.
🧰 Field Reference: What Your Technician Will Inspect
For homeowner safety, DIY replacement tools are disabled on this fault code. Your certified electrician or technician should bring:
- •Digital Multimeter (Continuity & 24V DC)
- •Phase Rotation Meter (For SUN-G03 3-Phase String)
- •External RSD Wiring Diagram
Don't Risk High-Voltage Shock with Deye Error F22
This fault involves internal bridge or DC intermediate capacitor stages. Under NEC & UL guidelines, probing energized solar conductors can cause lethal arc flash. Get competitive quotes from licensed solar electricians in your postal area:
❓ Frequently Asked Questions
Does Deye Error F22 mean my inverter is overheating?
No! Overheating / IGBT Heat Sink temperature is Fault F64 on Deye hybrids. Error F22 strictly means Emergency Stop / Rapid Shutdown (Tz_EmergS_Fault) on Deye hybrid models.
Can kids bumping an outdoor Rapid Shutdown switch cause Error F22?
Yes—this is one of the single fastest real-world causes. Outdoor emergency mushroom buttons latch down with one light bump and require twisting the red head clockwise to release.
Why does my SUN-G03 string manual list F22 differently?
Deye's older grid-only three-phase string series maps F22 to Transient Leakage or Phase Sequence rotation rather than Hybrid Emergency Stop loops—always verify by unit model.
Related Deye Fault Codes
Inverter failed startup GFDI ground-relay verification or detected mismatched grid/neutral earthing configuration.
Inverter sensed complete loss of external AC utility voltage on its Grid input terminals.
Cascade protection stopped parallel-connected hybrid inverters after a sibling inverter faulted (or High Grid Voltage on single string models).
Inverted positive and negative DC polarity detected across one or more PV MPPT string inputs.