Deye Error F35: No Utility Grid Detected (AC Loss / Outage)
Affected Models: Deye SUN-SG04LP1, SUN-SG04LP3, SG05LP1, SG01HP3 & SUN-G03 String Series
⚡ Quick Engineering Answer
Deye • Error F35Deye Error F35 means AC No Utility Fault (AC_NoUtility_Fault)—the inverter senses zero utility voltage on its Grid AC input terminals. Common causes are an active neighborhood power blackout, a tripped external solar AC isolator/breaker in your switchboard, or a blown utility fuse. Homeowners can safely check utility power and external AC breakers.
📊 Technical Specification & Trigger Matrix
- Official Manual Definition
- Inverter sensed complete loss of external AC utility voltage on its Grid input terminals.
- Trigger Threshold
- Measured AC Grid terminal voltage < 30V–50V RMS (complete grid loss)
- Recovery Window
- Auto-synchronizes within 60–300 seconds once street power returns smoothly
- Subsystem Affected
- AC Grid Input Voltage Sense & Main Breaker
- Warranty Outlook
- External outage or tripped breaker (0% inverter defect unless AC relays/fuses failed)
How Deye Error F35 Triggers
During an electrical utility blackout—or anytime someone flips off the dedicated Solar AC breaker inside the main switchboard—a hybrid Deye inverter intentionally isolates its Grid port relays to protect utility line workers (anti-islanding) while switching backup loads seamlessly onto battery/PV power, logging Error F35 (AC_NoUtility).
On pure grid-tied string models without batteries, F35 shuts output down completely until street voltage stabilizes. Note that on three-phase units, losing just ONE utility phase fuse outside at the street pole causes F35 even when some lights elsewhere in the house still glow dimly!
🔀 Hardware & Series Differences
Watch battery SoC% during prolonged blackouts and conserve heavy backup appliances.
Verify all three poles of the Solar AC isolator sit ON and utility power has all 3 phases.
🔍 Observable Symptoms
- •LCD displays Error F35 while Grid voltage icon reads 0V on the home power-flow diagram.
- •Backup LOAD lights keep running off battery (on hybrids) while non-backed-up main panel appliances shut dark.
- •Triggered during neighborhood grid outages or storms.
- •Persists when utility street power is working if the dedicated Solar AC breaker tripped OFF.
⚙️ Ranked Root Causes
Zero AC voltage from street feeder forces anti-islanding disconnect and logs F35.
Lightning transient or accidental switch bump opens AC grid circuit between meter and inverter.
One dead phase drops three-phase grid detection even though other home rooms stay lit.
High-resistance AC breaker lug burns open and drops grid sensing at the inverter.
🔄 Safe Shutdown & Reset Sequence Flow
Follow strict step order left-to-rightTest a regular wall outlet NOT on solar backup to see if utility grid power is actually out.
Ensure the labeled 'Solar / Inverter Main AC' circuit breaker sits fully ON (reset cleanly once if tripped).
Once AC utility supply stabilizes, F35 vanishes automatically after the grid countdown.
Safe External Scope: Do Not Open Covers or Probe Terminals
All checks below remain strictly outside the sealed enclosure (display apps, breaker sequence, airflow/filter clearances, or external plugs). Never open housing screws or expose live wiring.
🔧 Interactive Step-by-Step Diagnostic Checklist
Confirm Neighborhood Grid Power & External Switchboard Breakers
Check whether regular household grid outlets (like an oven or non-backup lights) have electricity and check your main electrical distribution box for a tripped Solar Inverter AC breaker or RCD switch. Flip a tripped breaker ON once—if it immediately trips back OFF, stop and call an electrician.
Read Incoming AC Grid Voltage in LCD Home Flow Screen
Tap the Grid tower icon on the front Deye touchscreen to view incoming L1/L2/L3 Grid voltage readings without opening any casing.
Conserve Backup Battery During Extended Blackouts
While grid stays down under F35, turn off high-drain non-essential appliances on backup circuits and inspect Battery SoC% inside Solarman so solar panels can keep recharging essentials through daylight.
📋 Ready-to-Send Technician Fault Brief
Completed safe checks without clearing Error F35? Copy this structured engineering summary for your installer or OEM RMA ticket.
📋 Homeowner Preparation & Read-Only Access Needed
No electrical test instruments or aftermarket tools are required for these checks—have the following ready before starting:
- ✓Deye Touchscreen Grid Voltage Flow Screen
- ✓Main Distribution Switchboard Access
- ✓Local Utility Outage Map
❓ Frequently Asked Questions
Does Deye Error F35 hurt my hybrid inverter?
Not at all! F35 is a harmless status indicator telling you utility grid power went missing (or the AC breaker switched off), while your hybrid safely supplies backup outlets from battery and solar.
Why does my inverter say F35 when half my house lights still turn on?
On homes with a three-phase connection, blowing a single street fuse leaves lights on two healthy phases working normally while the three-phase inverter detects one missing phase and safely disconnects!
If my Solar AC breaker keeps tripping off right after turning it back ON, what should I do?
Leave the breaker OFF immediately and call a qualified solar electrician—an instant trip means a dead short circuit in AC wiring or an internal inverter surge stage.
Related Deye Fault Codes
AC utility grid voltage (specifically Line W-U on 3-phase systems) dropped below the configured lower grid protection ceiling.
AC grid or generator port frequency exceeded upper permitted Grid Code ceiling (or EEPROM mismatch on legacy string units).
Inverter paused momentarily to re-initialize power relays after changing Battery, Grid Type, or Operating Mode settings.
Inverted positive and negative DC polarity detected across one or more PV MPPT string inputs.