SolarEdge Error Codes & Fix Guides
Industry-leading DC-optimized inverter systems with HD-Wave technology and power optimizers. Select or filter any fault code below for trigger parameters, reset order, and step-by-step troubleshooting.
SolarEdge Hardware Signal Topology
SolarEdge Diagnostic Profile (26 Codes)
SolarEdge Error 18x86: PV Isolation Fault (Earth Ground Leakage)
High-voltage DC string insulation resistance (`Riso`) dropped below safe earth isolation threshold on SetApp single-phase inverters.
SolarEdge Error 8x58: Three-Phase / Synergy Array Isolation Fault
Three-phase / Synergy inverter detected earth leakage across parallel DC solar strings dropping isolation resistance below 1 MΩ.
SolarEdge Error 18xC: DC Arc Fault Detected (AFCI Safety Lockout)
AFCI hardware detected electrical sparking on DC solar strings and safely locked out production to prevent fire.
SolarEdge Error 3x11: Arc Detection Status Interrupt (AFCI Fault)
Platform arc-detection interrupt (`3x11`) locked out solar output after sensing DC electrical arc signatures.
SolarEdge Error 18x8D: AFCI Self-Test Failed (Arc Sensor Hardware Check)
Internal AFCI arc-detection circuit failed its morning wake-up self-verification test.
SolarEdge Error 18xB5: Internal DC/AC In-Stage Overvoltage (Hardware RMA)
Internal HD-Wave DC/AC in-stage capacitor bus overvoltage fault requiring warranty inverter replacement.
SolarEdge Error 18xB7: Internal DC/AC Out-Stage Overvoltage (Hardware Fault)
HD-Wave output conversion stage registered internal overvoltage (`DC/AC out-stage overvoltage`), requiring inverter replacement.
SolarEdge Error 18xA6: Tz Over Voltage (Internal Bus Capacitor Voltage Event)
Internal capacitor bank overvoltage (`Tz Over Voltage`) tripped conversion shutdown from capacitor aging or AC surge.
SolarEdge Error 18x75: Overtemp (Internal Thermal Protection Shutdown)
Inverter overheated and temporarily suspended or throttled output due to high ambient temperature or obstructed airflow.
SolarEdge Error 18x37: V-Line Max (AC Grid Voltage Too High)
AC line voltage exceeded regional Country Setup ceiling (`V-Line Max`), pausing solar production temporarily.
SolarEdge Error 18x38: V-Line Min (AC Grid Voltage Too Low / Brownout)
Incoming utility AC line voltage fell below regional Country Setup minimum (`V-Line Min`), halting export.
SolarEdge Error 18x1D: AC Line-to-Neutral Voltage Above Threshold (V_LN Max)
Line-to-Neutral AC voltage exceeded safe threshold from utility overvoltage, country mismatch, or loose neutral reference.
SolarEdge Error 18x1E: AC Line-to-Neutral Voltage Below Threshold (V_LN Min)
Line-to-Neutral AC voltage fell below permissible lower threshold due to tripped breakers, brownouts, or poor neutral connection.
SolarEdge Error 18x20: AC Grid Voltage Below Country Limit (Vac Low)
AC output voltage fell below regional utility minimum, pausing export safely.
SolarEdge Error 18x21: AC Grid Voltage Above Limit (Vac High / Solar Rise)
AC line voltage exceeded regional overvoltage ceiling during export, pausing solar generation.
SolarEdge Error 2x22: AC Grid Frequency Above Limit (F_AC High)
AC line frequency exceeded configured utility ceiling, triggering anti-islanding halt.
SolarEdge Error 2x23: AC Grid Frequency Below Limit (F_AC Low)
Measured AC utility frequency dropped beneath regional minimum tolerance, pausing export to protect grid stability.
SolarEdge Error 18x1A: AC Grid Voltage Surge Transient (Vac Surge)
Instantaneous AC line voltage transient tripped hardware overvoltage protection, flagging potential surge-arrestor or loose-neutral hazard.
SolarEdge Error 18xC7: SafeDC Rapid Shutdown Test Failure (>30V DC)
SafeDC string voltage stayed above 30V DC during rapid shutdown verification on Energy Hub / SetApp inverters.
SolarEdge Error 3x6E: RS485 Energy Meter Communication Error
Inverter lost Modbus/RS485 telemetry link to the external Energy Meter, halting battery automation and zero-export control.
SolarEdge Error 3x6A: Inverter Remotely Locked / Safety Lock Active
Firmware security or critical safety lockout disabled inverter wake-up until authorized digital unlock via SolarEdge Portal / SetApp.
SolarEdge Error 3xB: No Country or Grid Profile Configured (Error 44)
Required regional utility Grid Code profile is missing or reset to unconfigured default, blocking AC grid connection.
SolarEdge Error 8x4F: Wrong Three-Phase AC Wiring / Phase Rotation (Error 112)
Commercial three-phase inverter detected incorrect phase sequence, missing neutral reference, or AC wiring mismatch at startup.
SolarEdge Error 8x2B: Three-Phase Ground / RCD Current Surge Fault
Residual Current Monitoring Unit detected an acute AC/DC earth-leakage spike during live generation, halting inverter output.
SolarEdge Error 2x1A: Internal AC Relay Failure (Error 26 / Grid Switch Fault)
Mechanical AC grid isolation relay failed startup self-check (welded shut or failing to latch), halting export safely.
SolarEdge Error 33xD: Internal Cooling Fan Failure (Fan Fault)
Cooling fan tachometer reported stalled RPM or open circuit under PWM drive, reducing midday thermal capacity.
No fault codes match the active filter combination.