Deye Error F18: Hardware AC Overcurrent Fault
Affected Models: Deye SUN-SG04LP1, SUN-SG04LP3, SUN-SG05LP1 & SUN-G03 Series
⚡ Quick Engineering Answer
Deye • Error F18Deye Error F18 indicates a fast hardware-level AC overcurrent trip (HW AC_OverCurr_Fault) on the inverter output or Backup Load port—triggered by excessive household surge appliances, dead AC short circuits, or failed current sensors/IGBTs. Safely turn off heavy backup appliances and sub-breakers to test unloaded reboot; wiring and board repairs require an electrician.
📊 Technical Specification & Trigger Matrix
- Official Manual Definition
- Hardware protection circuit detected sudden excessive AC output or grid port current past transistor ratings.
- Trigger Threshold
- Hardware AC current comparator tripped (> ~1.8x–2.5x rated peak output current)
- Recovery Window
- May auto-retry once; repeated trips lock out requiring breaker isolation + manual restart
- Subsystem Affected
- IGBT AC Bridge, Hardware Overcurrent Comparator & Backup Port
- Warranty Outlook
- Internal board/IGBT faults covered within warranty; external house short circuits excluded
How Deye Error F18 Triggers
Whereas software overload protections react over seconds, Deye Error F18 fires within microseconds via dedicated analog hardware comparators monitoring AC inverter legs. Its job is saving internal IGBT bridge transistors from exploding when confronted by downstream AC short circuits, grid fault transients, or huge off-grid compressor locked-rotor startup spikes.
In residential hybrid installations (SUN-5K/8K/12K-SG04LP1/LP3), F18 surfaces most frequently during off-grid power outages when heavy well pumps, split air conditioners, or hot water elements exceed the Backup LOAD port surge limit—or when an appliance shorts live-to-neutral. On units faulting repeatedly even unloaded with Grid/Backup breakers disconnected, suspect loose internal AC CT harnesses or blown IGBT gates.
🔀 Hardware & Series Differences
Check kW/surge draw on Backup LOAD panel (keep inductive motors within 1.5x–2x 10s surge window).
Immediate F18 with AC Grid + Backup Load breakers physically disconnected confirms internal hardware repair.
🔍 Observable Symptoms
- •Backup LOAD outlets drop dark immediately during blackout startup of large motors/pumps.
- •Touchscreen flashes Error F18 accompanied by loud relay click.
- •May coincide with F34 AC overcurrent alarms on heavy load transitions.
- •Repeats instantaneously on boot if output IGBT shorted.
⚙️ Ranked Root Causes
Water pumps, compressors, or shorted wiring exceed instantaneous peak AC output amps.
Step utility voltage drops force reactive surge currents across tied grid relays.
Open/floating hardware sense harness sends false peak spikes to comparator.
Internal power transistor failure draws instantaneous hardware overcurrent every startup.
🔄 Safe Shutdown & Reset Sequence Flow
Follow strict step order left-to-rightTurn off AC pumps, heaters, and backup panel breakers completely before testing reboot.
Allow internal DC bus capacitors to drain completely until screen turns black.
If F18 trips while completely unloaded, power off permanently and call service.
High-Voltage / Refrigerant Safety Boundary: Pro Service Split
Steps tagged "Homeowner Safe" below are strictly external read-only or external breaker inspections. Steps tagged "Licensed Technician" involve energized DC/AC bus voltages, isolation testing, or sealed refrigerant circuits—never attempt those steps without certification.
🔧 Interactive Step-by-Step Diagnostic Checklist
Disconnect Backup Appliances & Sub-Breakers for Load Test
Switch off heavy backup circuit breakers (air conditioning, well pumps, water heaters) in your home sub-panel, turn external inverter switches OFF for 3 minutes, then restart unloaded.
Check Solarman Load Graphs Right Before Fault
Inspect Load Power (kW) on individual L1/L2/L3 phases in Solarman right before F18 logged to spot phase overloads on three-phase SG04LP3 units.
Test Output AC Wiring Megger & Isolate All Field Cables
De-energize inverter safely, check L-N-PE resistance on field Backup and Grid wiring for shorts, disconnect external AC wires completely, and run standalone battery-only self-test.
Rebalance Phase Loads / Install Soft-Starter or Replace Power Board
Rebalance high-draw backup loads across three phases or fit soft-starters to deep-well pumps; replace faulted IGBT power board under warranty if unloaded F18 locks.
📋 Ready-to-Send Technician Fault Brief
Completed safe checks without clearing Error F18? Copy this structured engineering summary for your installer or OEM RMA ticket.
🧰 Field Reference: What Your Technician Will Inspect
For homeowner safety, DIY replacement tools are disabled on this fault code. Your certified electrician or technician should bring:
- •AC True-RMS Clamp Meter (Inrush Mode)
- •Insulation Continuity Tester
- •Load Phase Balancing Diagram
Don't Risk High-Voltage Shock with Deye Error F18
This fault involves internal bridge or DC intermediate capacitor stages. Under NEC & UL guidelines, probing energized solar conductors can cause lethal arc flash. Get competitive quotes from licensed solar electricians in your postal area:
❓ Frequently Asked Questions
What is the difference between Deye F18 and F34?
Both monitor AC output current: F18 is an instant hardware comparator trip triggered by extreme short circuits or sharp surges, while F34 tracks slower continuous/software AC overcurrent.
Can running a heavy well pump or microwave during a power outage cause F18?
Yes! On 120/240V or single-phase hybrids, high startup inrush current on an AC motor exceeding inverter peak rating triggers instantaneous F18 hardware cutoff.
If F18 pops up with all house breakers turned OFF, is the inverter broken?
Most likely yes—either an internal current-sense wire loosened or an internal IGBT output module failed and requires Deye service/RMA.
Related Deye Fault Codes
AC output load on the Backup/UPS port exceeded continuous current ratings (or internal comms timeout on select string models).
Fast analog hardware protection tripped due to excessive DC current surge on the PV or battery converter stage.
Internal NTC temperature sensor reading out of bounds on Deye hybrids, or AC overcurrent trip on grid-tied string models.
Inverted positive and negative DC polarity detected across one or more PV MPPT string inputs.
Reviewed and verified by the VoltFaults Engineering Standards Team. All diagnostic procedures, safety warnings, and component tests are cross-referenced directly with original manufacturer service documentation and international electrical safety codes (UL 1741, IEEE 1547 & IEC 62109).