Deye Error F24: DC Insulation Impedance Failure (Riso Fault)
Affected Models: Deye SUN-SG04LP1, SUN-SG04LP3, SUN-SG05LP1, SG01HP3 & SUN-G03 String Inverters
⚡ Quick Engineering Answer
Deye • Error F24Deye Error F24 means DC Insulation Impedance Failure (DC_Insulation_Fault / low Riso)—not an AC current sensor fault (which old blogs wrongly claim). Before connecting solar relays at dawn, the inverter detected low resistance between PV strings and earth ground caused by soaked connectors, pinched cables, or shattered panels. Switch PV OFF safely; string megger diagnostics require a technician.
📊 Technical Specification & Trigger Matrix
- Official Manual Definition
- Pre-startup insulation resistance test failed between rooftop PV array conductors and Protective Earth ground.
- Trigger Threshold
- Array insulation resistance (Riso) drops below safe startup floor (typically < 100–500 kΩ / 1 MΩ)
- Recovery Window
- Re-tests periodically or on restart; persists permanently while damaged string remains soaked/shorted
- Subsystem Affected
- PV String Insulation Sensing Circuit & Rooftop Cabling
- Warranty Outlook
- Internal board sensing defect covered by warranty; roof water/rodent leaks billed as array repair
How Deye Error F24 Triggers
Every morning before engaging MPPT boost stages, Deye hybrid and string inverters inject a tiny safe test voltage between the solar DC inputs and chassis Protective Earth (PE) to measure array Riso (Insulation Resistance). Under IEC 62109 safety compliance, if resistance between either PV+ or PV- to earth drops below statutory limits (often <100 kΩ–1 MΩ depending on voltage class), Error F24 locks solar power offline cleanly.
Notice how F24 differs from F16/F23: F24 tests insulation health statically BEFORE active inversion begins (commonly catching rain-soaked MC4 connectors pooling in roof gutters, mouse-chewed DC sheathing inside attic conduits, water inside a rooftop DC isolator, or cracked solar glass backsheets). Never bypass F24 earthing checks—ungrounded DC ground faults create severe roof fire hazards.
🔀 Hardware & Series Differences
Commonly strikes first on wet mornings after hailstorms, roof work, or rodent damage.
Ensure modern transformerless Deye PV strings always run strictly floating relative to Earth.
🔍 Observable Symptoms
- •Inverter locks out early morning with Error F24 while refusing PV harvest all cloudy/wet day.
- •Often unlocks partially on hot dry afternoons only to return every damp sunrise.
- •Exterior rooftop DC isolator housing shows moisture condensation inside.
- •Visible darkened or blistered backsheet on an old solar panel.
⚙️ Ranked Root Causes
Waterproof seals degrade or lose gaskets when mounted pointing upright in roof gutters.
Sharp metal tile edges or attic rodents expose bare copper strands to wet structures.
Hail or thermal aging lets rainwater penetrate live PV laminates to aluminum frame.
Internal sensing failure falsely triggers F24 even with external PV switch OFF.
🔄 Safe Shutdown & Reset Sequence Flow
Follow strict step order left-to-rightIsolate the leaking solar array completely before walking around metal framing.
Boot inverter on battery/AC only to verify error stems externally from solar strings.
Do not climb wet roofs or disconnect DC solar strings yourself; live PV remains hazardous.
High-Voltage / Refrigerant Safety Boundary: Pro Service Split
Steps tagged "Homeowner Safe" below are strictly external read-only or external breaker inspections. Steps tagged "Licensed Technician" involve energized DC/AC bus voltages, isolation testing, or sealed refrigerant circuits—never attempt those steps without certification.
🔧 Interactive Step-by-Step Diagnostic Checklist
Run PV-Isolated Inverter Check & Review Rain Logs
Switch external PV rotary isolator OFF completely (leaving battery/AC switches ON) and perform one quick controller reboot to verify F24 doesn't trigger when rooftop wires stay disconnected.
Look Visually Around Exterior DC Isolator & Conduit (No Touching)
From ground level safely check whether water trails, broken roof conduit, or cracked exterior DC switch boxes are visible near the inverter wall.
Measure PV1 / PV2 Insulation Resistance With 500V/1000V Megger
Isolate DC safely, unplug each string independently, check VOC-to-ground voltage first (high Voc-to-ground pinpoints faulted panel location along series string!), then run 500V/1000V insulation megger across string +/- to Earth.
Re-Terminate Wet Splices / Replace Faulted Module & Verify >100 MΩ
Replace flooded MC4 connectors, replace degraded conduit or wet DC switches, swap delaminated panels, secure zip-ties off roof surfaces, and verify Riso exceeds >100 MΩ before reconnecting inverter.
📋 Ready-to-Send Technician Fault Brief
Completed safe checks without clearing Error F24? Copy this structured engineering summary for your installer or OEM RMA ticket.
🧰 Field Reference: What Your Technician Will Inspect
For homeowner safety, DIY replacement tools are disabled on this fault code. Your certified electrician or technician should bring:
- •1000V DC Insulation Resistance Tester (Megger)
- •True-RMS Multimeter (Voltage-to-Ground Method)
- •IP68 Matched MC4 Connectors & Cable Ties
Don't Risk High-Voltage Shock with Deye Error F24
This fault involves internal bridge or DC intermediate capacitor stages. Under NEC & UL guidelines, probing energized solar conductors can cause lethal arc flash. Get competitive quotes from licensed solar electricians in your postal area:
❓ Frequently Asked Questions
Does Deye Error F24 mean an AC current sensor calibration error?
No—that is outdated/wrong data on some blogs. Official Deye service manuals designate Error F24 strictly as DC Insulation Impedance Failure (low Riso between solar strings and earth).
How can a solar technician find the exact bad panel out of 12 panels in a string?
Using the Voltage-to-Ground method! Measuring Voc from Positive-to-Earth and Negative-to-Earth points accurately to the percentage point along the series string where moisture bridges to metal framing.
Can spraying water on dusty solar panels trigger Deye Error F24?
Yes—if water jets hit aged junction boxes or loose MC4 couplings lying directly under modules on hot tiles, rapid capillary moisture drop triggers F24 immediately.
Related Deye Fault Codes
Inverter internal GFCI sensor measured excessive continuous leakage current to ground (>300mA safety limit).
Internal GFCI/RCMU protection caught a sharp instantaneous step spike in AC/DC earth leakage current.
Inverted positive and negative DC polarity detected across one or more PV MPPT string inputs.
Inverter failed startup GFDI ground-relay verification or detected mismatched grid/neutral earthing configuration.