Fronius State 560: Power Reduction Due to Over-Frequency (Grid Support P(f))
Affected Models: Fronius Primo, Symo, Eco & GEN24 Plus
⚡ Quick Engineering Answer
Fronius • State 560Fronius State 560 means active Power Reduction Due to Over-Frequency (P(f) grid support mode)—NOT a SolarNet loop defect! When neighborhood grid or backup microgrid AC frequency creeps past regional standards (commonly >50.2 Hz or >60.5 Hz), Fronius smoothly ramps wattage down rather than tripping abruptly offline. It self-clears automatically once AC frequency normalizes.
📊 Technical Specification & Trigger Matrix
- Official Manual Definition
- Inverter actively curtailed output power to help stabilize grid frequency above standard over-frequency start point.
- Trigger Threshold
- Utility or microgrid AC frequency enters regional P(f) droop band (typically 50.2–51.5 Hz or 60.2–61.5 Hz)
- Recovery Window
- Auto-clears immediately once frequency settles safely back inside nominal band (50.0 / 60.0 Hz)
- Subsystem Affected
- Active Power Regulation P(f) & PLL Frequency Loop
- Warranty Outlook
- 100% normal compliant behavior (0% inverter fault unless Country Setup wrong)
How Fronius State 560 Triggers
Under modern grid codes (VDE-AR-N 4105, EN50549, AS4777, IEEE 1547-2018), solar inverters help utilities stabilize electrical grid frequency smoothly instead of tripping offline suddenly. Whenever surplus solar or load drops push local utility frequency gently past 50.2 Hz (or 60.5 Hz), Fronius State 560 (Derating caused by over-frequency) proportionally reduces AC output power (P(f) droop curve).
Microgrid / Off-Grid Battery Bonus: On homes combining Fronius PV inverters AC-coupled onto Victron/off-grid battery inverters or diesel backup generators, State 560 is critical and completely normal! Once off-grid batteries approach 95%–100% full charge, the battery inverter bumps AC frequency deliberately up to 50.3–51.5 Hz so Fronius throttles smoothly with State 560—matching PV generation exactly to house load before jumping to full cutoff (State 105).
🔀 Hardware & Series Differences
P(f)) power throttling above utility start point (e.g., >50.2 Hz)Compare cleanly with State 567 (over-voltage throttling) and State 105 (complete over-frequency trip).
Requires MG50/MG60 microgrid frequency-response setup for buttery-smooth battery charge control without frequent full disconnects.
🔍 Observable Symptoms
- •State 560 logs repeatedly in Solar.web notifications on off-grid battery systems during sunny afternoon fullness.
- •Output power drops softly toward household consumption wattage right after batteries reach ~98% SoC.
- •Pressing Enter dismisses notice temporarily without affecting active generation.
- •Occasional State 560 flashes on utility grids during national emergency frequency-stabilization events.
⚙️ Ranked Root Causes
Victron MultiPlus/Quattro and off-grid inverters bump Hz slightly from 50.2 to 51.0 Hz to signal smooth curtailment.
Slightly fast generator mechanical speed activates smooth P(f) curtailment immediately.
Local grid over-generation triggers coordinated droop curtailment across connected smart inverters.
Overly strict country droop starts throttling under minor everyday grid swings.
🔄 Safe Shutdown & Reset Sequence Flow
Follow strict step order left-to-rightView real-time Hz in Solar.web/LCD and verify whether batteries hit 98%–100% on off-grid/AC-coupled sites.
Output recovers automatically when battery draws load or utility Hz settles back toward 50.0 / 60.0 Hz.
Ask your off-grid installer to disable redundant State 560 alert emails if cycling daily as intended.
Safe External Scope: Do Not Open Covers or Probe Terminals
All checks below remain strictly outside the sealed enclosure (display apps, breaker sequence, airflow/filter clearances, or external plugs). Never open housing screws or expose live wiring.
🔧 Interactive Step-by-Step Diagnostic Checklist
Confirm Utility Grid vs Off-Grid Battery Curtailment Context
Check whether batteries sit nearly full on an AC-coupled off-grid home or if standby generators run when State 560 logs—if so, State 560 confirms smooth solar power throttling is working perfectly.
Compare Active Country Profile & Grid Frequency Telemetry
View System Info > Country Setup safely on LCD/WebUI to verify your correct country code is displayed and check logged Hz spikes right when power dropped.
Request Off-Grid / MG50 Fine-Tuning If Curtailment Cycles Harshly
If State 560 cycles harshly on off-grid battery setups or backup generators, share Solar.web frequency graphs with your installer so they can apply Fronius MG50/MG60 tuning or calibrate generator speed.
📋 Ready-to-Send Technician Fault Brief
Completed safe checks without clearing State 560? Copy this structured engineering summary for your installer or OEM RMA ticket.
📋 Homeowner Preparation & Read-Only Access Needed
No electrical test instruments or aftermarket tools are required for these checks—have the following ready before starting:
- ✓Fronius Solar.web Service Message Log
- ✓Inverter System Info Menu (View-Only)
- ✓Off-Grid Battery / Generator User Guide
❓ Frequently Asked Questions
Does Fronius State 560 mean my SolarNet data cable broke?
NO! That is a common internet myth. Officially across Fronius SnapINverter and GEN24 manuals, State 560 specifically indicates over-frequency active power reduction (P(f)).
Why do I get State 560 every sunny afternoon with my Victron battery system?
Your battery inverter purposefully shifts grid frequency up slightly (~50.3–51.0 Hz) once batteries approach 100% so your Fronius throttles smoothly without overcharging cells—100% normal!
Will clearing State 560 give me more free daytime power on grid-tie?
No—once local neighborhood grid frequency settles safely back down to 50.0/60.0 Hz, full solar output restores automatically on its own.
Related Fronius Fault Codes
Utility grid or backup generator AC frequency exceeded upper permitted limit, pausing solar feed-in.
Inverter scaled back export power under Volt-Watt rules because local grid voltage rose high.
Inverter proactively lowered maximum AC wattage output to prevent overheating under hot conditions or restricted cooling.
AC grid voltage exceeded upper statutory protection limit, pausing solar feed-in to protect home appliances and grid stability.
Reviewed and verified by the VoltFaults Engineering Standards Team. All diagnostic procedures, safety warnings, and component tests are cross-referenced directly with original manufacturer service documentation and international electrical safety codes (UL 1741, IEEE 1547 & IEC 62109).